Hungary 220KV Power Transformer

Our company's 220kV oil-immersed energy-saving transformers feature low losses, low noise, low temperature rise, high reliability, zero leakage, and are maintenance-free. All technical specifications meet internationally advanced standards.

Product Description

Our company's 220kV oil-immersed energy-saving transformers feature low losses, low noise, low temperature rise, high reliability, zero leakage, and are maintenance-free. All technical specifications meet internationally advanced standards.

 

They are widely used in the power systems of power plants, substations, renewable energy wind farms and photovoltaic power plants, as well as large-scale industrial and mining enterprises such as the petrochemical industry. These 220kV oil-immersed energy-saving transformers include both on-load and off-excitation voltage regulation types, suitable for three-phase, 50Hz, power systems operating at voltages of 220kV and below.

Product Parameters

 

S18-220KV 31500KVA-240000KVA Power Transformer

Rated Capacity (KVA)

Voltage Combination and Tapping Range

Vector Group

No Load Loss (KW)

Load Loss (KW)

No Load Current (%)

Capacity Allocation (%)

Impedance (%)

HV (KV)

MV (KV)

LV(KV)

31500

220±8x1.25%  230±8x1.25%

69     115     121

6.3
6.6
10.5
21
36
37
38.5

YNyn0d11

28

145

0.77

100/100/100
100/50/100
100/100/50

HV-MV
12-14
HV-LV
22-24
MV-LV
7-9

40000

33

174

0.73

50000

38

205

0.74

63000

45

244

0.69

90000

10.5
21
36
37
38.5

58

315

0.54

120000

74

390

0.54

150000

86

463

0.48

180000

99

568

0.48

240000

120

704

0.43

 

S22-220KV 31500KVA-240000KVA Power Transformer

Rated Capacity (KVA)

Voltage Combination and Tapping Range

Vector Group

No Load Loss (KW)

Load Loss (KW)

No Load Current (%)

Impedance (%)

HV (KV)

LV (KV)

31500

220±8x1.25%
230±8x1.25%

6.3
6.6
10.5
21
36
37
38.5

YNd11

20

115

0.48

12-14

40000

23

134

0.5

50000

28

161

0.45

63000

33

188

0.45

90000

42

246

0.38

120000

10.5
21
36
37
38.5

51

304

0.38

150000

60

360

0.35

180000

70

413

0.32

120000

66

69

53

303

0.38

150000

62

355

0.37

180000

73

406

0.32

240000

91

504

0.25

Performance Advantages

 

1. Low Loss: Through specialized electromagnetic design and manufacturing processes, no-load losses are reduced by 20% and loaded losses by 5% compared to national standards, resulting in significant energy savings.

2. Low Noise: Exclusive noise reduction technology is applied in multiple locations to address electromagnetic and mechanical noise sources, reducing transformer noise by 3-5 dB(A) compared to national standards.

3. Strong Short-Circuit Resistance: The product has passed the sudden short-circuit test conducted by the National Transformer Quality Inspection and Testing Center, verifying its reliability in withstanding short-circuit shocks.

Structural Features

 

1. The core features a six-level joint, a fully inclined, non-porous structure, and a continuous upper and lower yoke design, effectively reducing no-load losses and noise.        
2. The fuel tank adopts a flat-top structure, with the top and bottom cut from a single piece of steel plate, providing strong overall rigidity. The tank is manufactured using a pre-assembled process, undergoes rigorous leak testing, and is sandblasted for rust removal to ensure high-quality coating and long-term corrosion resistance.

TSTY's Advantages

 

TSTY Electric Co., Ltd is a national high-tech enterprise with a history of more than 30 years, focusing on the intelligent manufacturing of power transmission and distribution equipment. It mainly deals in oil-immersed, dry-type transformers, box-type substations, high and low voltage switchgear and have obtained ISO 9001, CCC, CE, IEC, UL,GOST and other certifications, 158 patents, and are exported to more than 100 countries.  

Factory scale: 250,000 square meters of park, 15 production lines (including 3 intelligent lines), equipped with 220+ intelligent equipment.  

Production capacity efficiency: annual production capacity:25000 units transformer+ 10000 HV LV switchgear, product qualification rate> 99.8%.

TSTY VS Others

 

Process

TSTY Approach

Conventional Practice

Bolt Material

Stainless-steel bolts · Prevent corrosion-related seizure

Standard galvanized bolts · May seize after years of exposure

Corner Treatment

Rounded corners · Improved coating adhesion

Sharp corners retained · Greater risk of coating peeling

Surface Pretreatment

Shot blasting + pickling + phosphating

Basic grinding or direct painting

Coating System

C5-class electrostatic powder coating · 150 μm · >1,000 h salt-spray resistance

Conventional paint · 90–100 μm

Lifting Protection

Rubber protective sleeves · Damage-free handling and delivery

Wire ropes in direct contact · Risk of impact and coating damage

 

Project Case

 

TSTY products are exported to more than 100 countries and regions, serving power projects in various regions.

Certificates

 

All TSTY transformer products have passed CE, IEC,UL, SGS, GOST and other certifications.